i-on160 Installer Menu Options
Page 47
Type: Active when: Assign to
Partitions?
this output type depends on whether
DD243 is on or off:
DD243 Confirmation Off – The output
does not operate.
DD243 Confirmation On – The output
activates when a second alarm zone is
triggered within the period of the
confirmation timer, and in the same
partition as the first alarm zone to be
triggered.
If the unconfirmed alarm is caused by the
expiry of the entry timer, a further two
zones which are not on the entry route
must be triggered to activate the output.
RF Low Battery
(08)
A wirefree detector reports a low battery.
The output remains active until all
detectors stop reporting low batteries.
Yes
RF Supervision
(09)
There is a supervision failure on any radio
zone. The output remains active until all
supervision failures are reset.
Yes
RF Jammin
(10)
The control unit detects
ammin
. The
output remains on until all jamming
disappears.
No
RF Fault (11) There are any of the following faults: RF
Low Battery, RF supervision, RF jamming.
Yes
Panel A/C Fail
(12)
Either Mains power is absent for between
52 and 59 minutes, OR a zone of type
“External PSU A/C Fail” has been triggered.
The control unit deactivates the output if a
user keys in a valid access code after
mains power has been restored.
Note: If the External PSU A/C Fail zone is
activated while the control unit is still
receiving mains power then the control unit
will activate this output within a few
seconds.
If the control unit is not receiving mains
power then it assumes that there is a
general power cut and waits for 52 to 59
minutes.
No