i-on160 Appendix I
Page 155
SIA3: #AAAAAA|Ntihh:mm/idnnn/rinn/CCcc
#AAAAAA|AS
Extended
SIA 3:
#AAAAAA|Ntihh:mm/idnnn/rinn/CCcc/AS
Where:
AAAAAA 6-digit programmable account code (e.g. 123456).
“N” New Event (always N).
“ti”hh:mm/ time (e.g. ti10:23/).
id”nnn/ user number, if applicable; otherwise not sent (e.
g
.
id123/ or id6/).
ri”nn/ partition no. (e.
g
. ri12/ or ri3).
CC event code (e.g. FA = Fire Alarm).
cc zone or keypad number, if applicable; otherwise
not sent (e.g. 23 or 5).
A”S text description of event, usually the lo
g
event
description.
(The control unit sends those characters shown between “ and “ above literally
as they appear in the text.)
For example, if there is a fire alarm on zone 2 of partition 4 at 10:15 (partition
4 account number is 10), the message would be:
SIA1: #000010|NFA2
SIA2: #000010|N/ri4
/
FA2
SIA3: #000010|Nti10:15/ri4/FA2 #000010|AFire
Zone 2
Extended SIA3: #000010|Nti10:15/ri4/FA2/AFire Zone 2