4. Programming
496964 Page 65
Value Type Description
13 Anti-Mask
Zone (AM)
Use this zone type for the outputs of detectors that
have an Anti-Mask output facility; these have to be
connected to two zones. Connect the detector's alarm
and contact wiring to one zone and its Anti-Mask
outputs to the zone above. Assign the Anti-Mask type
to the higher of the two zones; that is, the one
connected to the Anti-Mask outputs. This zone type is
active when the system is unset, and during setting
and unsetting. If the zone is violated, the control unit
starts a Tamper Alarm, shows the message "AM
Tamper" on the keypad display, and logs the event to
the zone number one below that assigned the Anti-
Mask type; that is, the one connected to the detector's
alarm and contact wiring.
14 Forbikobler
(FB)
This zone type is a Scandinavian type of Entry/Exit
zone (the word "forbikobler" means "bypass" in
Danish). Use this type for zones connected to
standalone external keypads or access controllers. If
the zone is triggered by the external keypad during the
exit time, the control unit stops the exit time and sets
the system. If the zone is triggered while the system is
set, the control unit starts the entry time. Use zone
attribute X7 to select an entry timer for the zone (page
67) and Commands 201–4 (page 116) to set up the
entry timers.
Zone Attributes
The following table shows the values available for zone attribute, depending
on the zone type. To set an attribute, key in the appropriate value. To unset
the attribute, key in the value again.
Value Attribute Valid for Description
X1
Chime (C) Normal Alarm
(NA)
Final Exit
(FE)
Entry Route
(ER)
Shock
Analyser
(SA)
When enabled by the user, the system
makes a doorbell-like sound when any
zones programmed as "Chime" are
opened. This facility operates only
while the system is unset.
To make the Chime available from
keypad sounders but not internal
sounders, use Command 22 with
option 0.