4. Programming
496964 Page 57
Re-entering Programming Mode
You can go back into programming mode whenever the system is unset and
not in alarm:
Note: If you have selected defaults for Finland, Norway, Sweden or Denmark
(Command 0), you must enter a valid user code at this point.
1. Key in 0 followed by the Engineer Code (default 7890).
The display shows:
Installer Mode
You are now in programming mode.
Restoring the Access Codes (first stage reset)
If the User and/or Engineer Codes are lost, then:
1. First remove mains power and then open the case and disconnect the
battery.
2. Identify the NVM Reset pins and Kick Start pins on the main PCB (see
Figures 3 to 5).
3. Short the NVM Reset pins together using a small wire link. Short the Kick
Start pins together with another small wire link.
4 Reconnect the battery.
5. Remove the shorts from the NVM Reset pins and Kick Start pins.
The control unit loads the factory default access codes:
User 01: 1234, Engineer: 7890.
6. Close the control unit and apply mains power.
7. Carry out an engineer reset.