
4. Programming
Page 56 496964
Command Key in:
198 Fast Format Channel 8 (page 115)
198YnnY
n = See Command 191 for a list of options.
Default is 06 Technical Alarm
199 Display Zone Circuit Resistance
(page 133)
199Y
= Use the 1 and 3 keys to step through
the circuits.
200 Forbikobler Entry Timer (page 116)
200YnY
nYnYnY
n = 1 Entry Timer 1
2 Entry Timer 2
3 Entry Timer 3
4 Entry Timer 4
201 Entry Timer 1 (page 116)
201YnY
n = 1 10 seconds
2 20 seconds
3 30 seconds
4 45 seconds
5 60 seconds
6 120 seconds
Command Key in:
202 Entry Timer 2 (page 116)
202YnY
n = 1 10 seconds
2 20 seconds
3 30 seconds
4 45 seconds
5 60 seconds
6 120 seconds
203 Entry Timer 3 (page 116)
203YnY
n = 1 10 seconds
2 20 seconds
3 30 seconds
4 45 seconds
5 60 seconds
6 120 seconds
204 Entry Timer 4 (page 116)
204YnY
n = 1 10 seconds
2 20 seconds
3 30 seconds
4 45 seconds
5 60 seconds
6 120 seconds
Leaving Programming Mode
When all programming has been completed:
1. Key in "99 Y" at the keypad
The display shows:
99:Exit Eng ?
2. Press Y.
The display shows:
99:Checking Sys
followed by the time and date.
The system is now in user mode.
Note: If there is a fault, for example an open tamper circuit, the display shows
this and will not return to Day mode. Press
X
and rectify the fault.
Performing an Engineer Reset
To perform an Engineer Reset:
1. Check that the display is showing the alarm condition.
2. Key in 0 followed by the Engineer Code (default 7890), followed by 99
YY.
The display shows the time and date.
Comentarios a estos manuales