2. Programming Commands
Page 16 497096, issue 3
27: Exit Fault External Sounder
This command controls what happens when an exit timer completes and a
zone is still violated (for example, when a door is not shut).
Option
0 Internal (default). System operates the internal sounders only.
1 Local. System operates both internal and external sounders.
Note: Compliance with PD 6662 / prEN 50131-1: 2004 (see page 85) prohibits an alarm
after a failure to set the system, which would require Command 27 to be set to
option 0. However, if external sounders are preferred, 9x5x control units also
provide "Set Fail" outputs that can be used to indicate that an alarm resulted from a
set failure.
28: Status Display
If you select option 0 (the default), the keypad displays "Level Set" or "Partn.
Set" continuously for the whole time that the alarm system is set. The keypad
lamps are illuminated if a relevant condition exists. Select option 1 to clear the
display and turn off the lamps 30 seconds after the user's last action.
The following table shows the effect of these settings in more detail.
Text Alert lamp Service/Mains lamps
Panel Set 0
continuous
1
timed
0
continuous
1
timed
0
continuous
1
timed
No alerts P/L set P/L set
30s, then
T&D
Off Off On On* 30s
Alerts P/L set P/L set
30s, then
T&D
On On 30s On On* 30s
Panel Unset 0
continuous
1
timed
0
continuous
1
timed
0
continuous
1
timed
No alerts T&D T&D Off Off On On* 30s
Alerts T&D T&D On On On On* 30s
P/L Partition or level T&D Time and date * If a relevant condition exists
Note: Compliance with PD 6662 / prEN 50131-1: 2004 (see page 85) at Grades 1, 2 and
3 requires that Command 28 is set to option 1.