5. Testing
Printing the Log
To print the event log, make sure the system is in programming mode, then
Key in 90 0.
Figure 24 below shows a sample of a printed log.
- 9851 -
14/12/01 18:42:30 Sounder Tamper
<END OF LOG>
Figure 24. Sample Log Print
To stop printing press .
To print a listing of the panel's configuration key in 90 8 .
Testing Outputs (Commands 91-96)
You may test parts of the system by entering commands at the keypad. To
carry out a test make sure the system is in programming mode and then key
in one of the following commands. Press to end each test:
91 To test output 1 (usually the external sounder/bell).
92 To test output 2 (usually the strobe output).
93 To test output 3.
94 To test the internal sounder output. (This command is not available in a
partitioned system.)
95 To test the keypad sounder.
96 To test output 4.
Engineer Walk Test (Command 97)
Allows the engineer to test all devices on the system.
1. Enter programming mode.
2. Key in 97
The display shows:
3. Open and close each alarm and tamper contact in turn.
The system gives a chime tone each time you open and close a detec-
tor contact. The displays shows: "A:Zone:" and the zone number of
every detector you have tested (note that the display shows each zone
number for one second, in sequence). If you also test the tampers on
each zone the display shows the letter "T" against each zone number.
4. Press to stop the walk test.
Note that the Engineer's walk test allows you to test all zones including PA
zones, zone tampers, and control unit and bell tampers. The user's walk test
does not allow you to test PA, Fire, 24Hr, Technical zones, or tampers.