9651 Programming - Programming Commands
11772232 Page 61
140: Fault Override
Use this command to determine how alerts can be overridden for all faults that
do not have an individual override command.
Option
0 Never (default). The user cannot override a Fault alert when setting
the system.
1 Inactive. The user can override a Fault alert when setting the system,
provided that the cause of the fault has been rectified.
Note: Overrides faults including AC Fail, Aux DC, Battery Load Test Fail,
Battery Missing, Comms Fail, Keypad Ident Fail, Line Fail, Low Battery,
Plugby Fail, uCom Fail, Zone AC Fail, Zone Battery Fault, Zone Fault,
Zone Low Battery and Zone Pwr O/P.
141: Alert Tone On/Off
Use this command to disable the Alert fault tones. When enabled (default) the
system gives an alert tone and displays alerts on the keypad.
Option
0 Disabled. The display shows alert messages for faults, but does not
sound alert tones.
1 Enabled (default). The display shows alert messages, and the system
gives alert tones.
151 to 158: Plug-by Communicator Outputs
These commands select types for the control unit's programmable outputs,
which can be used to control a plug-by communicator. The 9651 provides
eight programmable outputs on the main circuit board. The outputs can be
connected to the communicator by a wiring harness provided with the control
unit (refer to the 9x5x Installation Guide for details). The commands take two
digits to select the type and have the following defaults:
Command Output Default type
151 1 01 Fire
152 2 02 PA
153 3 03 Burglar
154 4 04 Open/Close
155 5 15 Zone Omitted
156 6 05 Alarm Abort
157 7 Not used
158 8 06 Technical Alarm