Programming - Programming Commands 9651
Page 54 11772232
3 30 seconds
4 45 seconds
5 60 seconds
6 120 seconds
Note: You cannot change the operation of Final Exit and Entry Route zones
assigned to Level D as you can with Levels B and C (see Commands 60,
61, 70 and 71). For this reason, Cooper Security recommends that you
use Level D for simple applications only.
80: Forbikobler Chime
This command links the bell push on the Forbikobler keypad to the Chime on
the system, so that pressing the bell operates the sounders.
Option
0 Off. Pressing the bell push does not operate the sounders (default).
1 On. Pressing the bell push operates the sounders.
81 to 83: Output n Type
These commands select types for the control unit's panel outputs. They take
two digits to select the type (see below) and have the following defaults:
Command Output Default outputs
81 1 00 Bell
82 2 08 Strobe
83 3 03 Set Latch
Notes: The panel outputs can be tested using Command 91 (page 71).
Option
00 Bell: active during an alarm. Use Command 41 to set Bell Delay and
42 to set Bell Duration. If Alarm Confirmation (Command 89) is
enabled, use Command 162 to set whether the bell is sounded on the
first or confirmed alarm.
01 EE Follow: active when Entry or Exit Time starts and inactive when
the time expires or is terminated. The output can be used for a
separate Entry/Exit buzzer. It will not give a tone during part set if the
exit mode is silent set or instant set.
02 Armed Lamp: active continuously while the system is full or part set.